Skip to content
Airdynex Engineering Private Limited
AIRDYNEX
Start page

Duct sizing

Detailed duct sizing by equal friction or velocity method. Round and rectangular options with velocity limits per application, Darcy–Weisbach friction and all rectangular alternatives for tight ceiling voids.

Inputs

L/s
Method
Pa/m

0.8 Pa/m (≈ 0.1 in. per 100 ft) is the usual low-pressure design rate. Use 0.5–0.6 for quiet rooms.

General offices, retail, schools, NC 35–40.

Duct section
m/s

Recommended for offices and commercial main: 8.0 m/s.

mm

Set this when the ceiling void limits the depth of a rectangular duct.

Cross-sections

To scale · same airflow
RoundØ355 mmRectangular450 × 200 mm
Round duct
Ø355 mm
4.0 m/s · 0.54 Pa/m
Rectangular duct
450 × 200 mm
4.4 m/s · 0.88 Pa/m · aspect 2.3:1

The exact diameter for this airflow is 327 mm, set by the friction rate. Sizes are rounded up to fabricated sizes.

Rectangular options

Size (W × H)VelocityFrictionAspectEq. Ø
450 × 200 mm4.40.882.3:1321
350 × 250 mm4.60.871.4:1322
300 × 300 mm4.40.791.0:1328

Velocity in m/s, friction in Pa/m. Only sizes up to 4:1 are listed.

Request a quote on WhatsAppEmail

Next step