Duct sizing
Detailed duct sizing by equal friction or velocity method. Round and rectangular options with velocity limits per application, Darcy–Weisbach friction and all rectangular alternatives for tight ceiling voids.
Inputs
L/s
Pa/m
0.8 Pa/m (≈ 0.1 in. per 100 ft) is the usual low-pressure design rate. Use 0.5–0.6 for quiet rooms.
General offices, retail, schools, NC 35–40.
m/s
Recommended for offices and commercial main: 8.0 m/s.
mm
Set this when the ceiling void limits the depth of a rectangular duct.

Duct sizing
airdynex.com/tools · 2026-11-28
Cross-sections
To scale · same airflowRound duct
Ø355 mm
4.0 m/s · 0.54 Pa/m
Rectangular duct
450 × 200 mm
4.4 m/s · 0.88 Pa/m · aspect 2.3:1
The exact diameter for this airflow is 327 mm, set by the friction rate. Sizes are rounded up to fabricated sizes.
Rectangular options
| Size (W × H) | Velocity | Friction | Aspect | Eq. Ø |
|---|---|---|---|---|
| 450 × 200 mm | 4.4 | 0.88 | 2.3:1 | 321 |
| 350 × 250 mm | 4.6 | 0.87 | 1.4:1 | 322 |
| 300 × 300 mm | 4.4 | 0.79 | 1.0:1 | 328 |
Velocity in m/s, friction in Pa/m. Only sizes up to 4:1 are listed.