Air device selection
Select diffusers or grilles for a room with full ASHRAE comfort checks: NC rating, pressure drop, throw distance and ADPI guidance for ceiling, sidewall and slot outlets.
Room and outlet
ADX-SQD. Louver-face diffuser for 600×600 T-bar ceilings. Horizontal throw along the ceiling in four directions.
NC 30 bedrooms and meeting rooms, 35 offices and classrooms, 40 retail and restaurants.

Concept view
Live · updates with your inputsPlan layout
Throw 4.0 m · T/L 1.99 · good ADPI range2 rows × 3 across, spaced 4.0 m × 4.0 m. Arrows show the four jets meeting at the midpoints and walls; throw to 0.25 m/s is 4.0 m.
Other layouts
| Outlets | Size | Each | NC | Pt | Throw · T/L | Choose |
|---|---|---|---|---|---|---|
| 6 (2×3) | 150×150 | 67 L/s | 20 | 41 | 4.0 · 1.99 | |
| 8 (2×4) | 150×150 | 50 L/s | 13 | 23 | 3.0 · 1.99 | |
| 9 (3×3) | 150×150 | 44 L/s | 11 | 18 | 2.7 · 1.99 | |
| 10 (2×5) | 150×150 | 40 L/s | 10 | 15 | 2.4 · 1.99 |
Neck sizes in mm. Pt in Pa; throw in m. T/L is throw divided by the distance to the wall or to the midpoint between outlets. ASHRAE links the band shown to good occupant comfort (ADPI). Performance is from generic catalogue data until Airdynex test data is loaded.
Specification textA clause to paste into your specification or BOQ.
SQUARE CEILING DIFFUSER, 4-WAY (ADX-SQD) Supply and install Airdynex ADX-SQD square louver-face ceiling diffusers with a removable core of fixed deflection louvers giving a four-way horizontal discharge, for lay-in to a 600 × 600 mm T-bar grid or surface mounting. Frame and core of extruded aluminium (6063-T5), polyester powder coated, colour RAL 9010 white [or as selected by the Architect]. Size: 150×150 mm. Quantity: 6 nos.. Selected for 67 L/s each, with a noise level not exceeding NC 20, total pressure not exceeding 42 Pa and a throw of about 4.0 m to 0.25 m/s terminal velocity. Provide an opposed blade volume control damper operable from the face where shown, and concealed fixing. Performance to be confirmed by the manufacturer's published data before approval. Submit shop drawings and samples for approval.