Detailed duct sizing by equal friction or velocity method. Round and rectangular options with velocity limits per application, Darcy–Weisbach friction and all rectangular alternatives for tight ceiling voids.

Inputs

L/s
Method
Pa/m

0.8 Pa/m (≈ 0.1 in. per 100 ft) is the usual low-pressure design rate. Use 0.5–0.6 for quiet rooms.

General offices, retail, schools, NC 35–40.

Duct section
m/s

Recommended for offices and commercial branch: 6.0 m/s.

mm

Set this when the ceiling void limits the depth of a rectangular duct.

Cross-sections

To scale · same airflow
RoundØ200 mmRectangular200 × 150 mm
Round duct
Ø200 mm
2.6 m/s · 0.50 Pa/m
Rectangular duct
200 × 150 mm
2.8 m/s · 0.66 Pa/m · aspect 1.3:1

The exact diameter for this airflow is 182 mm, set by the friction rate. Sizes are rounded up to fabricated sizes.

Rectangular options

Size (W × H)VelocityFrictionAspectEq. Ø
200 × 150 mm2.80.661.3:1189

Velocity in m/s, friction in Pa/m. Only sizes up to 4:1 are listed.